Model 6463A can output from primary current of 5 A to secondary current with in-phase error ±20 ppm (at 50Hz, 0Ω load) and quadrature phase error 20μrad (at 50Hz, 0Ω load). Therefore it can be used as a standard current transformer for various calibration operation. Combined with model 6040A and 6462A wider range of currents become available.
Item/Model | TYPE 6463A |
Primary Current Rating | 5 A (max. 10A) |
Secondary Current Rating | 5 mA,10 mA,20 mA,50 mA |
Frequency | 50 Hz to 400 Hz |
In-Phase Error | 20 ppm (at 50Hz, 0Ω load) 30 ppm (at 400Hz, 0Ω load) |
Quadrature Phase Error | 20μrad (at 50Hz, 0Ω load) 60μrad (at 400Hz, 0Ω load) |
Rated Load | 0.025 VA (at 50 mA Range) |
Secondary Short, Primary Input Equivalent AC Resistance | Less than 1Ω |
Power Supply | 100 Vac、50/60 Hz、1 A |
Size (WxDxH) mm | 450×430×130 |
Weight | Approx. 7 kg |