HOME 〉 PRODUCTS 〉 Current Transformer 〉 Error Compensation Current Transformer (Standard Current Transformer) TYPE 6460A

Error Compensation Current Transformer (Standard Current Transformer) TYPE 6460A

Error Compensation Current Transformer (Standard Current Transformer)  TYPE 6460A

Model 6460A can output secondary current against primary current(5A) ratio error 10ppm and phase angle error 10µrad in accuracy where setting range is within 0-120%. It is convenient to expand the area of current value in every calibration works. Also, using it with Model 6462A as a set, you can create more expanded current range.

Features

  • High accurate secondary current can be gained against setting value due to two-step structured transformer with compensating coil.
  • Secondary current can be output in one percent resolution accuracy in the area 0-120%.
  • Remotely controllable via standard IEEE-488 interface.
  • Model 6460A is durable for long term use because it is contained in aluminum-alloyed system case and transformer is molded.

Specifications

Primary Current5A(Maximum10A)
Secondary CurrentWithin 0 - 120% against primary current(Resolution 1%)
Frequency50Hz to 400Hz
Ratio Error10ppm
Phase Angle Error10µrad
Rated Burden25VA
GPIB InterfaceEquipped as standard
Power Supply100V ac (50Hz to 60Hz)
Dimensions(W/H/D)450 / 130 / 430 (mm)
WeightAbout15Kg
  • Model 6460A was developed under the technical guidance of JEMIC(Japan Electric Meters Inspection Corporation). Production and sales of this model is performed in accordance with a contract with them.
  • SunJEM accepts to produce other products with customer’s specification.
  • Specifications are subject to change without notice due to improvement
  • SunJEM will design products to meet your individual requirements.
    Please feel free to consult with us for products other than ready-made ones.